Sign In | Join Free | My himfr.com
Home > B&R Automation Plc >

X20SO6300 B&R X20 PLC SYSTEM I/O Module 6 Safe Digital Outputs With 0.2 A

Joyoung International Trading Co.,Ltd
Trust Seal
Verified Supplier
Credit Check
Supplier Assessment
Contact Now
    Buy cheap X20SO6300 B&R X20 PLC SYSTEM I/O Module 6 Safe Digital Outputs With 0.2 A from wholesalers
     
    Buy cheap X20SO6300 B&R X20 PLC SYSTEM I/O Module 6 Safe Digital Outputs With 0.2 A from wholesalers
    • Buy cheap X20SO6300 B&R X20 PLC SYSTEM I/O Module 6 Safe Digital Outputs With 0.2 A from wholesalers
    • Buy cheap X20SO6300 B&R X20 PLC SYSTEM I/O Module 6 Safe Digital Outputs With 0.2 A from wholesalers
    • Buy cheap X20SO6300 B&R X20 PLC SYSTEM I/O Module 6 Safe Digital Outputs With 0.2 A from wholesalers

    X20SO6300 B&R X20 PLC SYSTEM I/O Module 6 Safe Digital Outputs With 0.2 A

    Ask Lasest Price
    Brand Name : B&R
    Model Number : X20SO6300
    Certification : COC
    Price : USD
    Payment Terms : T/T
    Supply Ability : 10EA
    Delivery Time : 3-5 DAYS
    • Product Details
    • Company Profile

    X20SO6300 B&R X20 PLC SYSTEM I/O Module 6 Safe Digital Outputs With 0.2 A

    X20SO6300 B&R X20 PLC SYSTEM I/O Module 6 Safe Digital Outputs With 0.2 A
    MATERIAL NUMBER:

    X20SO6300

    DESCRIPTION:
    • 6 safe digital outputs with 0.2 A
    • Source circuit
    • Output type B
    • Integrated output protection

    This module is equipped with 6 safe digital outputs. The nominal output current is 0.2 A.

    The module can be used for controlling actuators in safety-related applications up to PL e or SIL 3.

    The outputs are designed using semiconductor technology so that the safety-related characteristics do not depend on the number of operating cycles. The "high-side high-side" variant (output type B) is required for actuators with reference potential (e.g. Enable inputs on frequency inverters). It is important to observe the special notices for the cabling in this case. Safe digital output channels provide protection against automatic restart when network errors occur.

    This module is designed for X20 12-pin terminal blocks.

    Short description
    I/O module6 safe type B1 digital outputs, 24 VDC, 0.2 A, OSSD <10 µs
    General information
    B&R ID code0xB815
    System requirements
    Automation Studio3.0.81.15 or later
    Automation Runtime3.00 or later
    SafeDESIGNER2.70 or later
    Safety Release1.2 or later
    mapp Technology Packagemapp Safety 5.7.0 or later
    Status indicatorsI/O function per channel, operating state, module status
    Diagnostics
    Module run/errorYes, using LED status indicator and software
    OutputsYes, using LED status indicator and software
    Blackout mode
    ScopeModule
    FunctionModule functionality
    Standalone modeNo
    Max. I/O cycle time1 ms
    Power consumption
    Bus0.32 W
    Internal I/O1.4 W
    Additional power dissipation caused by actuators (resistive) [W]1.128
    Electrical isolation
    Channel - BusYes
    Channel - ChannelNo
    Certifications
    CEYes
    Functional safetycULus FSPC E361559
    Energy and industrial systems
    Certified for functional safety
    ANSI UL 1998:2013
    Functional safetyIEC 61508:2010, SIL 3
    EN 62061:2013, SIL 3
    EN ISO 13849-1:2015, Cat. 4 / PL e
    IEC 61511:2004, SIL 3
    Functional safetyEN 50156-1:2004
    ATEXZone 2, II 3G Ex nA nC IIA T5 Gc
    IP20, Ta (see X20 user's manual)
    FTZÚ 09 ATEX 0083X
    ULcULus E115267
    Industrial control equipment
    HazLoccCSAus 244665
    Process control equipment
    for hazardous locations
    Class I, Division 2, Groups ABCD, T5
    DNVIn preparation
    EACYes
    KCYes
    Safety characteristics
    EN ISO 13849-1:2015
    CategoryCat. 3 if parameter "Disable OSSD = Yes - Warning",
    Cat. 4 if parameter "Disable OSSD = No"
    PLPL d if parameter "Disable OSSD = Yes - Warning",
    PL e if parameter "Disable OSSD = No"
    DC>60% if parameter "Disable OSSD = Yes - Warning",
    >94% if parameter "Disable OSSD = No"
    MTTFD2500 years
    Mission timeMax. 20 years
    IEC 61508:2010,
    IEC 61511:2004,
    EN 62061:2013
    SIL CLSIL 2 if parameter "Disable OSSD = Yes - Warning",
    SIL 3 if parameter "Disable OSSD = No"
    SFF>60% if parameter "Disable OSSD = Yes - Warning",
    >90% if parameter "Disable OSSD = No"
    PFH / PFHd
    Per channel<1*10-10
    openSAFETY wiredNegligible
    openSAFETY wireless<1*10-14* Number of openSAFETY packets per hour
    PFD<2*10-5
    Proof test interval (PT)20 years
    I/O power supply
    Nominal voltage24 VDC
    Voltage range24 VDC -15% / +20%
    Integrated protectionReverse polarity protection
    Safe digital outputs
    Quantity6
    VariantFET, 2x positive switching, type B1, output level readable
    Nominal voltage24 VDC
    Nominal output current0.2 A
    Total nominal current1.2 A
    Output protectionSee section "Inrush current behavior for output channels".
    Braking voltage when switching off inductive loadsMax. 45 VDC
    Error detection time1 s
    Insulation voltage between channel and bus500 Veff
    Peak short-circuit currentSee section "Inrush current behavior for output channels".
    Leakage current when the output is switched off<100 µA
    RDS(on)4.7 Ω
    Switching voltageI/O power supply minus voltage drop due to RDS(on)
    Max. switching frequencySee section "Inrush current behavior for output channels".
    Test pulse lengthMax. 10 µs
    Max. capacitive load100 nF
    Current on loss of ground
    IOUT<100 µA
    IGND<70 mA
    Operating conditions
    Mounting orientation
    HorizontalYes
    VerticalYes
    Installation elevation above sea level0 to 2000 m, no limitation
    Degree of protection per EN 60529IP20
    Ambient conditions
    Temperature
    Operation
    Horizontal mounting orientation0 to 60°C
    Vertical mounting orientation0 to 50°C
    DeratingSee section "Derating".
    Storage-40 to 85°C
    Transport-40 to 85°C
    Relative humidity
    Operation5 to 95%, non-condensing
    Storage5 to 95%, non-condensing
    Transport5 to 95%, non-condensing
    Mechanical properties
    NoteOrder 1x safety-keyed terminal block separately.
    Order 1x safety-keyed bus module separately.
    Pitch25+0.2mm
    Quality X20SO6300 B&amp;R X20 PLC SYSTEM I/O Module 6 Safe Digital Outputs With 0.2 A for sale