Sign In | Join Free | My himfr.com
Home > B&R Automation Plc >

X20AO4622 B&R X20 System PLC I/O Module 4 Analog Outputs ±10 V Or 0 To 20 MA / 4 To 20 MA

Joyoung International Trading Co.,Ltd
Trust Seal
Verified Supplier
Credit Check
Supplier Assessment
Contact Now
    Buy cheap X20AO4622 B&R X20 System PLC I/O Module 4 Analog Outputs ±10 V Or 0 To 20 MA / 4 To 20 MA from wholesalers
     
    Buy cheap X20AO4622 B&R X20 System PLC I/O Module 4 Analog Outputs ±10 V Or 0 To 20 MA / 4 To 20 MA from wholesalers
    • Buy cheap X20AO4622 B&R X20 System PLC I/O Module 4 Analog Outputs ±10 V Or 0 To 20 MA / 4 To 20 MA from wholesalers
    • Buy cheap X20AO4622 B&R X20 System PLC I/O Module 4 Analog Outputs ±10 V Or 0 To 20 MA / 4 To 20 MA from wholesalers
    • Buy cheap X20AO4622 B&R X20 System PLC I/O Module 4 Analog Outputs ±10 V Or 0 To 20 MA / 4 To 20 MA from wholesalers

    X20AO4622 B&R X20 System PLC I/O Module 4 Analog Outputs ±10 V Or 0 To 20 MA / 4 To 20 MA

    Ask Lasest Price
    Brand Name : B&R
    Model Number : X20AO4622
    Certification : COC
    Price : USD
    Payment Terms : T/T
    Supply Ability : 10EA
    Delivery Time : 3-5 DAYS
    • Product Details
    • Company Profile

    X20AO4622 B&R X20 System PLC I/O Module 4 Analog Outputs ±10 V Or 0 To 20 MA / 4 To 20 MA

    X20AO4622 B&R X20 System PLC I/O Module 4 Analog Outputs ±10 V Or 0 To 20 MA / 4 To 20 MA


    MATERIAL NUMBER: X20AO4622 B&R X20 System PLC I/O Module 4 Analog Outputs ±10 V Or 0 To 20 MA / 4 To 20 MA

    X20AO4622

    DESCRIPTION:
    • 4 analog outputs
    • Either current or voltage signal possible
    • 13-bit digital converter resolution

    X20 analog output module, 4 outputs, 10 V or 0 to 20 mA / 4 to 20 mA, 13-bit converter resolution


    General information
    B&R ID code0x1BA3
    Status indicatorsI/O function per channel, operating state, module status
    Diagnostics
    Module run/errorYes, using LED status indicator and software
    Channel typeYes, using software
    Power consumption
    Bus0.01 W
    Internal I/O1.8 W (Rev. ≥ J0), 2.2 W (Rev. < J0)
    Additional power dissipation caused by actuators (resistive) [W]-
    Certifications
    CEYes
    UKCAYes
    ATEXZone 2, II 3G Ex nA nC IIA T5 Gc
    IP20, Ta (see X20 user's manual)
    FTZÚ 09 ATEX 0083X
    ULcULus E115267
    Industrial control equipment
    HazLoccCSAus 244665
    Process control equipment
    for hazardous locations
    Class I, Division 2, Groups ABCD, T5
    DNVTemperature: B(0 - 55°C)
    Humidity: B(up to 100%)
    Vibration: B(4 g)
    EMC: B(bridge and open deck)
    LRENV1
    KRYes
    ABSYes
    EACYes
    KCYes
    Analog outputs
    Output±10 V or 0 to 20 mA / 4 to 20 mA, via different terminals
    Max. output current10 mA at voltage >5 V
    15 mA at voltage <5 V
    Digital converter resolution
    Voltage±12-bit
    Current12-bit
    Conversion time300 µs for all outputs
    Settling time on output change over entire range500 µs
    Switch on/off behaviorInternal enable relay for startup
    Max. error
    Voltage
    Gain0.08%
    Offset0.05%
    Current
    Gain0.09%
    Offset0.05%
    Output protectionShort-circuit proof
    Output format
    VoltageINT 0x8001 - 0x7FFF / 1 LSB = 0x0008 = 2.441 mV
    CurrentINT 0x0000 - 0x7FFF / 1 LSB = 0x0008 = 4.883 µA
    Load per channel
    VoltageMax. ±10 mA, load ≥1 kΩ
    CurrentLoad max. 600 Ω (Rev. ≥ J0), 500 Ω (Rev. < J0)
    Short-circuit proofCurrent limiting ±40 mA
    Output filterFirst-order low-pass filter / cutoff frequency 10 kHz
    Max. gain drift
    Voltage0.015%/°C
    Current0.02 %/°C
    Max. offset drift
    Voltage0.032%/°C
    Current0.032%/°C
    Error caused by load change
    VoltageMax. 0.11%, from 10 MΩ → 1 kΩ, resistive
    CurrentMax. 0.5%, from 1 Ω → 600 Ω, resistive
    Nonlinearity<0.007%
    Insulation voltage between channel and bus500 Veff
    Electrical properties
    Electrical isolationChannel isolated from bus
    Channel not isolated from channel
    Operating conditions
    Mounting orientation
    HorizontalYes
    VerticalYes
    Installation elevation above sea level
    0 to 2000 mNo limitation
    >2000 mReduction of ambient temperature by 0.5°C per 100 m
    Degree of protection per EN 60529IP20
    Ambient conditions
    Temperature
    Operation
    Horizontal mounting orientation-25 to 60°C (Rev. ≥ J0), 0 to 55°C (Rev. < J0)
    Vertical mounting orientation-25 to 50°C (Rev. ≥ J0), 0 to 50°C (Rev. < J0)
    DeratingSee section "Derating".
    Storage-40 to 85°C
    Transport-40 to 85°C
    Relative humidity
    Operation5 to 95%, non-condensing
    Storage5 to 95%, non-condensing
    Transport5 to 95%, non-condensing
    Mechanical properties
    NoteOrder 1x terminal block X20TB12 separately.
    Order 1x bus module X20BM11 separately.
    Pitch12.5+0.2mm